Supply System 33 kV
Rated Insulation Voltage RMS 70 kV
PEAK 170 kV
Rated Current 1250A, 1600A, 2000A, 2500A, 3150A**
Rated Frequency 50 Hz
Short Time Withstand Current 31.5kA For 3 Second
Degree of Protection Overall IP:55
Internal Arc Classification Yes, Available upto 31.5kA for 1 sec
Communication Yes, Available on following-
RS485 Modbus
RJ45-Ethernet
IEC61850 (Open Protocol)
Fibre Optic Communication
Applicable Standard IEC 62271-200

**Note: With Force Cooling